4-8
Adp4K_ReadStatus
This function code is used to read the status of the ioLogik 4000
adapter.
C/C++
Arguments
Return Value
int Adp4K_ReadStatus ( int hConnection ,
WORD *wBusStatus,
WORD *wFPStatus,
WORD *wEWStatus,
WORD *wESStatus,
WORD *wECStatus);
hConnection: The handle for an I/O connection.
wBusStatus: Stores the bus status in numerical format.
The values are:
0: Normal Operation.
1: Bus Standby.
2: Bus Communication Fault.
3: Slot Configuration Failed.
4: No Expansion Slot.
wFPStatus: Stores the field power status in numerical
format. The values are:
0: 24 VDC Field Power On.
1: 24 VDC Field Power Off.
wEWStatus: Stores the Watchdog status in numerical
format. The values are:
0: No Error.
1: Watchdog activated.
wESStatus: Stores the Modbus Setup Error status in
numeric data format, supported by NA-4020
& NA-4021 only.
0: No Error.
1: Modbus Setup Error.
wECStatus: Stores the Modbus Checksum Error status,
supported by NA-4020 & NA-4021 only.
0: No Error.
1: Three continuous CRC/LRC checksum
errors have occurred since last restart, last
clear counters operation, or last power-up.
Succeed MXIO_OK.