Moxa M-1401 Manual Página 81

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 129
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 80
ioLogik MXIO DLL API Reference Direct I/O Command Sets
6-44
AI_ReadRaw
This function code is used to read the raw data value of a specific
analog input channel.
C/C++
Arguments
Return Value
int AI_ReadRaw ( int hConnection,
BYTE bytSlot,
BYTE bytChannel,
WORD * wValue);
hConnection: The handle for an I/O connection.
bytSlot: Slot number of the I/O module, from 1 to 32.
This parameter is inactive for the ioLogik
E2000 and R2000.
bytChannel: The desired channel.
wValue: A pointer to raw data value of the desired
analog input channel.
Succeed MXIO_OK.
Fail Refer
t
oRe
t
u
r
nCodes.
Analog Input Commands for ioLogik E2000, R2000
AI2K_ReadMins
This function code is used to read the minimize values of
contiguous A/I channels.
C/C++
Arguments
Return Value
int AI2K_ReadMins ( int hConnection,
BYTE bytStartChannel,
BYTE bytCount,
double dValue[ ]);
hConnection: The handle for an I/O connection.
bytStartChannel: Specifies the starting channel.
bytCount: The number of channels to read.
dValue: An array that stores the minimize values of
contiguous A/I channels; dValue[0] represents
the value of the starting channel. The unit is
VDC for the voltage module, and mA for the
current module.
Succeed MXIO_OK.
Fail R
e
f
e
r
t
o
R
et
ur
n
o
de
s
.
Vista de página 80
1 2 ... 76 77 78 79 80 81 82 83 84 85 86 ... 128 129

Comentários a estes Manuais

Sem comentários